Paper
27 March 2022 Uncertainty analysis of fiber optical current transformer on-site calibration
Author Affiliations +
Proceedings Volume 12169, Eighth Symposium on Novel Photoelectronic Detection Technology and Applications; 12169B7 (2022) https://doi.org/10.1117/12.2626693
Event: Eighth Symposium on Novel Photoelectronic Detection Technology and Applications, 2021, Kunming, China
Abstract
The on-site calibration of fiber optical current transformer is often influenced by the environmental factors, resulting in certain deviation of results. We proposed the sources of uncertainty in this paper, which mainly include: the uncertainty uA(ε) induced by the error of standard FOCT, the uncertainty uB(ε) induced by the field environment and improper operation method, and the uncertainty uC(ε) induced by the calibrator unit. In further, the uB(ε) is analyzed detailed. This component is mainly produced by temperature, vibration and inhomogeneous magnetic field. The experimental results show that the errors of temperature, vibration and inhomogeneous magnetic field are 0.020%, 0.051% and 0.049%, respectively. Finally, we can calculate the synthetic standard uncertainty and expanded uncertainty of the DC calibration (P=99%) are 4.8×10-4 and 1.4×10-3, respectively. And the synthetic standard uncertainty and expanded uncertainty of the AC calibration (P=99%) are 5.6×10-4 and 1.6×10-3 respectively. The results show that the scheme can satisfy the uncertainty requirements of the direct comparison method (0.5S level).
© (2022) COPYRIGHT Society of Photo-Optical Instrumentation Engineers (SPIE). Downloading of the abstract is permitted for personal use only.
Wei Gao, Guochen Wang, Yongguang Wang, Yuxin Zhao, and Hongze Gao "Uncertainty analysis of fiber optical current transformer on-site calibration", Proc. SPIE 12169, Eighth Symposium on Novel Photoelectronic Detection Technology and Applications, 12169B7 (27 March 2022); https://doi.org/10.1117/12.2626693
Advertisement
Advertisement
RIGHTS & PERMISSIONS
Get copyright permission  Get copyright permission on Copyright Marketplace
KEYWORDS
Calibration

Magnetism

Transformers

Magnetic sensors

Fiber optics

Temperature metrology

Wave plates

RELATED CONTENT


Back to Top